FDNYC G60 Practice Exam Questions
and Answers 100% Pass
All torch operators, an oxigen-fuel torch using any amount of oxigen and flamable gas and fire
guards must have a current ✔✔Certificate of Fitness
The Certificate of Fitness holder ✔✔must regulate the pressure and flow of oxygen and natural
gas to each torch.
if the torch operator for jewelry manufacture involves ✔✔any oxygen with any fuel gas
containers, the operator must be a C of F holder.
A Certificate of Fitness Holder must keep his or her certificate ✔✔on their person or otherwise
readily available for inspection by any representative of the fire Department
The easiest way to extinguish a fire caused by a leak is to ✔✔close the shutoff valve
Permits issued by the FDNY are required to conduct the following hot work: ✔✔storing, using
or handling oxygen and a flammable gas, storing, using or handling any flammable gas (e.g.
LPG or CNG or acetylene) in excess of
400 SCF. Storing, using or handling any oxidizing gas (e.g. oxygen) in excess of 504 SCF.
For LPG, 400 SCF is ✔✔approximately 47 lbs
the number of LPG containers for the storage, use, handling or transportation, requiring a permit
✔✔14.1 oz = 54 cont.
16.4 oz = 46 cont.
20 lbs = 3 cont.
33.5 lbs = 2 cont.
40 lbs = 2 cont.
100 lbs = 1 cont.
Portable LPG containers that are more than 16.4 oz and CNG containers with a capacity greater
than 8.7 SCF ✔✔must NOT stored, handled, or used indoors in the following occupancies (as
defined in the Building code): residential occupancies, factory and industrial occupancies;
educational occupancies; institutional occupancies, except as the commissioner may authorize by
rule.
Site-specific permit ✔✔may be a permanent permit or a temporary permit. Permanent permits
are valid for 12 months only
A city-wide permit is valid ✔✔up to 30 days
Permits shall be ✔✔readily available on the premise for inspection by Fire Department
representatives.
Hot work authorization should be issued by the responsible person, and it ✔✔must be available
for inspection by any representative of the department during the performance of the work, and
for 48 hours after the work is complete
FDNY permits ✔✔will be posted in a central location and recorded in a log book to assist in the
coordination of construction related activities.
CNG ✔✔Compressed Natural Gas.
For Citywide hot work operations, the Owner of the premises must be notified in writing at least
_ hours in advance prior to work beginning. ✔✔48
FDNY G60 PRACTICE TEST (2022/2023)
Rated A+
Sprinkler system must NOT be shut off or impaired while hot work is performed ✔✔Place damp
cloth guards on individual sprinkler heads
The person conducting the fire watch _ have other duties ✔✔CANNOT A portable fire extinguisher with a rating of __ is required and should be within _ feet travel distance hot work area ✔✔2-A:20-B:C///30 For ROOFING OPERATIONS, a portable fire extinguisher with a minimum rating of is
required ✔✔3-A:40-B:C
Fire watch on floors below is ✔✔required
The fire watch must continue for a minimum of _ minutes after the hot work is done ✔✔30
For any CNG or LPG torch operations, the first inspection shall be conducted _ minutes after completion. The second inspection shall be conducted after completion of torch
operations. ✔✔30 min///1 hour
The fire guard or fire watch personnel must complete a signed inspection report and it must be
submitted to and retained by the person in charge of the torch operations. ✔✔The report must be
made available and maintained on the premises for a minimum of 48 hours after the work is
complete.
Most common fuel gasses used in blowtorches are ✔✔LPG (butane, propane) natural
gas (methane) (either CNG or piped natural gasses)
Soldering and brazing temperatures are typically___ ✔✔840 degrees F
Oxy-acetylene generates the highest temperature which can reach up to _ ✔✔6000 degrees F Gas torches can exceed _ and are used for burning weeds, melting ice, or applying tar
to a roof ✔✔2000 degrees F
FDNYC G60 Practice Exam Latest
Update Already Passed
All torch operators, an oxigen-fuel torch using any amount of oxigen and flamable gas and fire
guards must have a currentTodos los operadores de sopletes, un soplete de combustible de
oxígeno que utilice cualquier cantidad de oxígeno y gas inflamable y los protectores contra
incendios deben tener una corriente ✔✔Certificate of FitnessCertificado de aptitud
The Certificate of Fitness holderEl titular del Certificado de aptitud ✔✔must regulate the
pressure and flow of oxygen and natural gas to each torch.Debe regular la presión y el flujo de
oxígeno y gas natural a cada antorcha.
if the torch operator for jewelry manufacture involvessi el operador de la antorcha para la
fabricación de joyas involucra ✔✔any oxygen with any fuel gas containers, the operator must be
a C of F holder.cualquier oxígeno con cualquier recipiente de gas combustible, el operador debe
ser titular de C de F.
A Certificate of Fitness Holder must keep his or her certificateUn certificado de aptitud física
debe conservar su certificado. ✔✔on their person or otherwise readily available for inspection by
any representative of the fire Departmenten su persona o de otra manera fácilmente disponible
para inspección por cualquier representante del Departamento de Bomberos
The easiest way to extinguish a fire caused by a leak is toLa forma más fácil de extinguir un
incendio causado por una fuga es ✔✔close the shutoff valvecerrar la válvula de cierre
Permits issued by the FDNY are required to conduct the following hot work:Se requieren
permisos emitidos por el FDNY para realizar el siguiente trabajo en caliente: ✔✔storing, using
or handling oxygen and a flammable gas, storing, using or handling any flammable gas (e.g.
LPG or CNG or acetylene) in excess of
400 SCF. Storing, using or handling any oxidizing gas (e.g. oxygen) in excess of 504
SCF.almacenar, usar o manipular oxígeno y un gas inflamable, almacenar, usar o manipular
cualquier gas inflamable (por ejemplo, GLP o GNC o acetileno) en exceso de 400 SCF.
Almacenar, usar o manipular cualquier gas oxidante (por ejemplo, oxígeno) en exceso de 504
SCF.
For LPG, 400 SCF isPara GLP, 400 SCF es ✔✔approximately 47 lbsaproximadamente 47 lbs
the number of LPG containers for the storage, use, handling or transportation, requiring a
permitel número de contenedores de GLP para el almacenamiento, uso, manipulación o
transporte, que requieren un permiso ✔✔14.1 oz = 54 cont.
16.4 oz = 46 cont.
20 lbs = 3 cont.
33.5 lbs = 2 cont.
40 lbs = 2 cont.
100 lbs = 1 cont.
Portable LPG containers that are more than 16.4 oz and CNG containers with a capacity greater
than 8.7 SCFContenedores portátiles de GLP de más de 16.4 oz y contenedores de GNC con una
capacidad superior a 8.7 SCF ✔✔must NOT stored, handled, or used indoors in the following
occupancies (as defined in the Building code): residential occupancies, factory and industrial
occupancies; educational occupancies; institutional occupancies, except as the commissioner
may authorize by rule.NO debe almacenarse, manipularse o usarse en interiores en las siguientes
ocupaciones (como se define en el código de construcción): ocupaciones residenciales,
ocupaciones industriales y de fábrica; ocupaciones educativas; ocupaciones institucionales, salvo
que el comisionado lo autorice por regla.
Site-specific permitPermiso específico del sitio ✔✔may be a permanent permit or a temporary
permit. Permanent permits are valid for 12 months onlypuede ser un permiso permanente o
temporal. Los permisos permanentes son válidos solo por 12 mese
G-60, G60, F-60 FIRE GUARD, F-60 Study
Material Already Passed
G-60 ✔✔Use of oxygen and flammable gasses, or LPG or CNG for any hot work
COF exception ✔✔Torch operations for jewelry
FDNY permit ✔✔Storing using or handling
oxygen and flammable gas
in excess of 400scf (LPG, CNG or scetylene)
oxidizing gass in excess of 504scf
Portable LPG must not be stored when the capacity of the container is greater than? ✔✔16.4 oz
Portable CNG containers must not be stored then the capacity is greater than? ✔✔8.7 SCF
Single standard portable LPG containers must not exceed? ✔✔100LBs in weight
Single CNG containers must not exceed? ✔✔381 SCF
LPG
400 SCF is approximately ✔✔47 lbs
Types of FDNY permits ✔✔Site specific permits
City wide permits
Transportation permits
Site specific permit can be? ✔✔Can be permenant or temperary
Permanent permits are valid for how long? ✔✔12 months only.
Permits and renewals require inspection and will expire adter twelve months.
Temporary permits may be valid from? ✔✔One day to 12 months depending on the construction
or operations needed.
City wise permit duration? ✔✔30 days
Hazards out end of day
Quantity of hazardous material being stored(maximum)? ✔✔5 gals gasoline
250 gals of flammable
300 gals combustible liquid
Transportation permit ✔✔FDNY approved inspected displayed on vehicle
Hot work authorization. ✔✔Required for any project with hot work operation but not issued by
the FDNY
Responsible person ✔✔Must be available for inspection by any representative of fire department
during and 48 hours after the work is complete.
Fire guard ✔✔Cof holder who is trained in and responsible for maintaijjng a fire watch.
Fire watch ✔✔Survailance of an area
Detect signs of early fire
Raise alarms
Notify department
Pre hot work check must be conducted by the responsible person before hot work is authorized at
least? ✔✔Once per day
Pre hot work check daily and must very the following ✔✔Equipment working in order
Hot work is clear of combistibles and flammable solids
Combustible and non combustible are protected
F-60 FIRE GUARD QUESTIONS AND
ANSWERS ALREADY GRADED A
THE COF HOLDER MUST KEEP THE COF OR READILY AVAILABLE FOR
INSPECTION ✔✔UPON HIS OR HER PERSON
PORTABLE LPG CONTAINERS THAT ARE MORE THAN MUST NOT BE
STORED, HANDLED, OR USED INDOORS. ✔✔16.4 OZ
PERMITS SHALL BE READILY AVAILABLE ON THE FOR INSPECTION BY
FIRE DEPARTMENT REPRESENTATIVES. ✔✔PREMISES
HOT WORK PERMITS SHALL BE AVAILABLE FOR INSPECTION BY ANY
REPRESENTATIVE FOR _ AFTER THE WORK IS COMPLETE. ✔✔48 HOURS
FOR ____, THE OWNER OF THE HOT WORK OPERATION AREAS MUST BE
NOTIFIED IN WRITING BY THE CITYWIDE PERMIT HOLDER AT LEAST 48 HOURS
BEFORE HOT WORK IS TO BE STARTED. ✔✔CITYWIDE HOT WORK OPERATIONS
PRE-HOT WORK CHECKS MUST BE CONDUCTED BEFORE HOT WORK IS
AUTHORIZED AND AT LEAST . ✔✔ONCE PER DAY
FIRE WATCH WILL BE PROVIDED FOR A MINIMUM OF AFTER WORK IS
COMPLETE. ✔✔30 MINUTES
HOT WORK AREAS MUST BE KEPT _ FEET AWAY FROM ANY
COMBUSTIBLE MATERIAL. ✔✔35
PAPER, WOOD SHAVINGS, STRAW AND FABRIC ARE EXAMPLES OF
__. ✔✔COMBUSTIBLE MATERIAL
THE ENTIRE WORK AREA SHOULD BE CHECKED AFTER COMPLETION OF HOT
WORK FOR _. ✔✔FIRES
A MINIMUM ___ RATING FIRE EXTINGUISHER MUST BE READILY
ACCESSIBLE. ✔✔2-A:20-B:C
G-60 Questions and Answers 100% Pass
G-60 ✔✔Use of oxygen and flammable gasses, or LPG or CNG for any hot work
COF exception ✔✔Torch operations for jewelry
FDNY permit ✔✔Storing using or handling
oxygen and flammable gas
in excess of 400scf (LPG, CNG or scetylene)
oxidizing gass in excess of 504scf
Portable LPG must not be stored when the capacity of the container is greater than? ✔✔16.4 oz
Portable CNG containers must not be stored then the capacity is greater than? ✔✔8.7 SCF
Single standard portable LPG containers must not exceed? ✔✔100LBs in weight
Single CNG containers must not exceed? ✔✔381 SCF
LPG
400 SCF is approximately ✔✔47 lbs
Types of FDNY permits ✔✔Site specific permits
City wide permits
Transportation permits
Site specific permit can be? ✔✔Can be permenant or temperary
Permanent permits are valid for how long? ✔✔12 months only.
Permits and renewals require inspection and will expire adter twelve months.