What is the lighting demand load (before derating) for a house with outside dimensions of 30 ft 48 ft on the first floor and 22 ft 42 ft on the second floor

What is the lighting demand load (before derating) for a house with outside dimensions of 30 ft 48 ft on the first floor and 22 ft 42 ft on the second floor? A one-family dwelling has a 175-ampere, 240-volt service that is fed with 75C (167F) conductors. What is the minimum size copper grounding electrode conductor required?

The correct answer and explanation is :

Lighting Demand Load Calculation:

To calculate the lighting demand load for the house, we use the National Electrical Code (NEC) guidelines for lighting load calculations. For a dwelling, the general lighting load is based on the square footage of the house.

  1. Calculate the total square footage of the house:
  • First floor:
    The first floor has dimensions of 30 feet by 48 feet.
    Total area of the first floor = 30 ft × 48 ft = 1,440 square feet.
  • Second floor:
    The second floor has dimensions of 22 feet by 42 feet.
    Total area of the second floor = 22 ft × 42 ft = 924 square feet.
  • Total square footage:
    Total area = 1,440 sq ft (first floor) + 924 sq ft (second floor) = 2,364 square feet.
  1. Lighting load based on NEC Table 220.12:
    According to the NEC, the general lighting load for a dwelling is calculated at 3 volt-amperes (VA) per square foot.
  • Lighting load = 2,364 sq ft × 3 VA/sq ft = 7,092 VA.

Thus, the lighting demand load for the house (before derating) is 7,092 VA or approximately 7.1 kVA.

Minimum Size Copper Grounding Electrode Conductor (GEC):

The grounding electrode conductor size is based on the service size and conductor temperature rating, per NEC Table 250.66.

  1. Service Size:
    The house has a 175-amp, 240-volt service.
  2. Temperature Rating of Conductors:
    The conductors are rated at 75°C (167°F).
  3. Find the minimum size GEC using NEC Table 250.66:
    According to Table 250.66, for a 175-amp service and 75°C conductor rating, the minimum required grounding electrode conductor size is based on the ampacity of the service. The value for 175 amps corresponds to a 6 AWG copper conductor for the grounding electrode.

Therefore, the minimum size copper grounding electrode conductor required is a 6 AWG copper wire.

Summary:

  • Lighting demand load: 7,092 VA or 7.1 kVA.
  • Minimum size copper GEC: 6 AWG.