UST EXAM LATEST FINAL 2024 ACTUAL EXAM
Local agency inspectors performing UST system inspections must meet
the following requirements: which of the following statements is most
accurate.
a.) Effective July 1, 2005 posses a current inspector certificate issued by
ICC
b.) Renew the CA UST Inspector Certification every 24 months by
either passing the ICC Cal. UST Inspector exam of satisfying equivalent
criteria as approved by the Board.
c.) Renew the CA UST Inspector Certification every 24 months by
passing the ICC Cal. UST Inspector exam
d.) Newly hired local agency inspectors are required to pass the CA UST
Inspector exam 120 days from the date of hire. – ANSWER- b.) Renew
the CA UST Inspector Certification every 24 months by either passing
the ICC Cal. UST Inspector exam of satisfying equivalent criteria as
approved by the Board.
Fiberglass tanks shall be repaired by the following, except:
a.) Small fractures and fissures may be repaired with epoxy
b.) Fiberglass cloth with a minimum dimension 12 x 12 inches centered
over the area to be repaired.
c.) A second layer of fiberglass cloth shall be installed directly over the
primary cloth layer and shall be cut to overlap the primary patch by 5
inches on all sides.
d.) The repaired tank shall be tested for tightness within 30 calendar
days following the date of the completion of the repair. – ANSWER- c.)
A second layer of fiberglass cloth shall be installed directly over the
primary cloth layer and shall be cut to overlap the primary patch by 5
inches on all sides.
CCR Title 23, Sec 2661(d)(4)
Tanks installed after July 1, 1987 with suction piping are exempt from
the requirement for secondary containment of the piping provided all the
following are met, except:
a.) No valves or pumps are installed below-grade in the suction line.
b.) The below-grade piping operates at less than atmospheric pressure.
c.) The below-grade piping is sloped so that the product will drain back
into the storage tank
d.) An angle check valve or check valve is located as near to the tank top
and as close to the dispenser pump as possible. – ANSWER- d.) An
angle check valve or check valve is located as near to the tank top and as
close to the dispenser pump as possible.
CCR Title 23, Sec 2636(a)(3)
Automatic line leak detectors shall be installed on underground
pressurized piping and shall be capable of detecting a 3-gallon per hour
leak rate at 10 psi within 1 hour with a probability of detection of at least
% and a probability of false alarm no greater than _%.
a.) 95, 5
b.) 98, 2
c.) 5, 95
d.) 2, 98 – ANSWER- a.) 95, 5
CCR Title 23, Sec 2636(f)(2) & 2643(c)(1)
An emergency impact valve (shear valve) is found in the following
location on an UST System.
a.) At the turbine piping termination
b.) Base of the dispenser
c.) Under the extractor tee
d.) Spill container – ANSWER- b.) Base of the dispenser
Underground storage tank owners and operators shall submit a copy of
the secondary containment test report to the local agency within _ of the completion of the test, a.) 60 days b.) 30 days c.) 45 days d.) 15 days – ANSWER- b.) 30 days CCR Title 23, Sec 2637(e) Notification to perform a secondary containment test must be given to the local agency by: a.) A service technician or a licensed tank tester. b.) Cathodic protection tester. c.) Owner/operator of UST. d.) State Water Resources Control Board. – ANSWER- c.) Owner/operator of UST CCR Title 23, Sec 2637(f) A tank integrity test is required every _ when statistical inventory
reconciliation is used.