PDF Download
FREE AND STUDY GAMES ABOUT CODEOLOGY 7 EXAM
QUESTIONS
Actual Qs and Ans Expert-Verified Explanation
This Exam contains:
-Guarantee passing score -18 Questions and Answers -format set of multiple-choice -Expert-Verified Explanation Question 1: 1. NEC 240.21, with some exceptions, requires overcurrent protection in each ungrounded conductor to be located where the conductors connect to the load.True False
Answer:
False Question 2: 11. Feeder taps not over 10 feet long are covered by NEC section ? .
- 240.21(A)
- 240.21(B)(1)
- 240.21(C)(3)
- 240.21(C)(6)
Answer:
- 240.21(B)(1)
Question 3: 14. A 25-foot, 4 AWG, 75°C, copper conductor could be tapped from a 3/0 AWG 75°C, copper feeder conductor protected by a 200-ampere OCPD, if the 4 AWG terminates in an 80 A OCPD and the tap conductors are protected from physical damage by being enclosed in an approved raceway.
- Acceptable Correct
- Violation Incorrect
Answer:
Acceptable Question 4: 6. Once a feeder conductor has been tapped with smaller tap conductors serving downstream equipment, it is not permissible to apply a second tap on the first tap. (In essence, do not tap a tap.)
- True
- False
Answer:
True
240.21
Question 5: 16. Which of the following is not a required item for tap conductors over 25 feet long used in a high bay manufacturing building over 35 feet high at the walls?
Answer:
- The tap conductors are sized 8 AWG copper or 2 AWG aluminum or larger.
Question 6: 17. As shown in the figure, a 150-ampere feeder conductor is installed outside the building in a metal wireway. A 60-ampere tap conductor is installed from the metal wireway to a new garage building located 100 feet away from the original building. A 60-ampere fused disconnecting means is provided outside the new garage. The tap conductors are protected from physical damage by a rigid metal conduit.
Answer:
Acceptable
Question 7: 10.The NEC permits a set of conductors feeding a single load, or each set of conductors feeding separate loads, to be connected to a transformer secondary without overcurrent protection at the secondary, as specified in ?
- 230.91
- 240.2 tap conductors definition
- 240.21(C)(1) through (C)(6)
- 450.3 I
Answer:
- 240.21(C)(1) through (C)(6)
Question 8: 7. A 3/0 AWG copper feeder conductor is tapped with 20 feet of 2 AWG conductor.What is the maximum OCPD size allowed at the termination of the tap conductors installed in a fused switch or circuit breaker? (All conductors and terminations are rated 75°C.
Select one:
- 100 A
- 110 A Correct
- 125 A
- 150 A
- 125 A
- 150 A
Answer:
- 110 A Correct
240.21(B) does not allow the use of 240.4(B), known as the round-up rule. The 2 AWG conductor ampacity from Table 310.15(B)(16) is 115 amperes. The standard rating for OCPDs shown in 240.6(A) would therefore require a 110-ampere OCPD to be used.
Question 9: 15. In an industrial installation, three separate 400-ampere bus duct taps, each 40 feet in length, are permitted to be tapped from a 1,200-ampere busway protected by a 1,200-ampere OCPD.
Answer:
Acceptable -368.17(B) Exception Question 10: 8. An existing 50-ampere branch circuit is located in a kitchen for the connection of cooking equipment. A tap conductor is used to supply a new wall-mounted oven and a new counter-mounted cooking unit. The wiring method used between the 50-ampere junction box and the new cooking equipment is Type NM cable. What is the minimum size conductor and maximum conductor length allowed by Code for this installation?
- 12 AWG, 50' Incorrect
- 10 AWG, 50' Incorrect
- 12 AWG, unlimited length, but not longer t
Answer:
- 12 AWG, unlimited length, but not longer than necessary
Note: 240.21(A) references 210.19 and this installation is addressed by 210.19(A)(3) Exception No.
1.
The correct answer is: 12 AWG, unlimited length, but not longer than necessary
Question 11: 19. A service conductor is never a tap conductor.
Answer:
True Question 12: 4 .Tap conductors shall be permitted to be protected against overcurrent in accordance with ? .
- 210.19(A)(4)
- 240.21
- 368.17(B)
- 430.53(D)
- All of the above