Question 1: T/F
NFPA 70E 225.3 Circuit Breaker Testing states that "Circuit breakers that interrupt faults approaching their ratings shall be inspected and tested in accordance with the manufacturer's instructions."
Answer:
True Question 2: It is necessary to select a separate overload protective device for a 25-horsepower continuous-duty motor with 32 amperes nameplate current rating and a marked 1.15 service factor. Table 430.250 shows 34 amperes for such a motor. What is the maximum trip setting or ampere rating permitted for this overload protective device? Assume that the more permissive requirements of 430.32(C) are not warranted.
- 32 A
- 34 A
- 40 A
- 42.5 A
Answer:
- 40 A
Question 3: Match the correct Interrupting Range for each type of fuse.
-Class G fuse
- 200kA
B. 100KA
- 200kA or 300kA
- 10kA
Answer:
B. 100KA
Question 4: T/F
Supplementary OCPDs are described as OCPDs permitted for only specific branch-circuit applications, under limited conditions, per the specific reference in the NEC.
Answer:
False
Question 5: Feeder taps not over 10 feet long are covered by NEC section ____?
- 240.21(A)
- 240.21(B)(1)
- 240.21(C)(3)
- 240.21(C)(6)
Answer:
- 240.21(B)(1)
Question 6: T/F
A Type ICCB uses electronic sensor technology.
Answer:
True
Question 7: Generally, the overload element of a branch-circuit dual-element time-delay fuse will hold an overload that is five times greater than the ampere rating of the fuse for a minimum time of _____
- 2 seconds
- 5 seconds
- 10 seconds
- 20 seconds
Answer:
- 10 seconds
- higher
- lower
Question 8: Refer to the figures and follow the steps outlined in the short-circuit calculation procedure.Calculation of Fault Currents - Figure 10Calculation of Fault Currents - Figure 11 The short circuit at position 7 is ? than the short-circuit current at position 6
Answer:
- lower
Question 9: T/F
Instantaneous trip circuit breakers are also referred to as motor circuit protectors (MCPs) and are intended only for motor branch circuit short-circuit and ground-fault protection.
Answer:
True
Question 10: Match the correct Memory Word for each type of fuse......
Class T fuse
- rejection
- Tiny
- large
- junior
Answer:
- Tiny
Question 11: Match the correct Ampere Rating Range for each type of fuse.
-Class H fuse
- Fractional - 30A
B. 1-100A
C. 1/2 - 60A
D. 1/8 - 600A
Answer:
D. 1/8 - 600A
Question 12: T/F
Supplementary overcurrent protection is used for luminaires, appliances, and other equipment and can be used as a substitute where branch-circuit overcurrent devices are required.
Answer:
false Question 13: Under fault conditions, the greatest damage done to components by a fault current often occurs in the first half-cycle. What are the most common results of a fault current to electrical components?
- Explosive vaporization of the metal conductors and conductive parts
- Heating of components to high temperatures can cause deterioration of insulation
- Tremendous magnetic forces between conductors can crack insulators and loosen or rupture
- both
- and
- a., b.,
bracing structures or equipment.
b.
Answer:
- a., b., and c.