Backflow Repair Technician Certification Exam (ASSE 5130) Practice Test Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- Which component in a reduced pressure principle assembly discharges
- Shutoff valve #2
- Relief valve
- First check valve
- Test cock #1
water during normal operation?
Rationale: The relief valve between the checks opens under normal
pressure fluctuations to maintain protection.
2. The major function of a check valve in a backflow assembly is to:
- Filter debris
- Allow bidirectional flow 1 / 3
- Regulate flow rate
- Prevent reverse flow
Rationale: Check valves are one-direction components that stop reverse
flow caused by backpressure or backsiphonage.
3. A reduced pressure zone assembly provides protection against:
- Pollution only
- Residential cross-connections
- Both pollution and contamination under backpressure or backsiphonage
- Fire sprinkler water only
Rationale: RPZ assemblies offer the highest level of mechanical backflow
protection.
- The correct order of components in a double check valve assembly from
inlet to outlet is:
- Shutoff, relief valve, check valve, test cocks
- Test cocks, check valve, shutoff
- Shutoff #1, check #1, test cocks, check #2, shutoff #2
- Relief valve, check valves, shutoff
Rationale: DCA assemblies always have check valves placed between two
shutoff valves.
5. The relief valve in an RP assembly must discharge to:
- Any direction
- Atmosphere
- A closed drain 2 / 3
- The downstream line
Rationale: Atmospheric discharge ensures reduced pressure zone integrity
if checks fail.
6. When testing a DCA, the minimum required check valve closure is:
- 1.0 psid
- 1.0 psid minimum across each check
- 5.0 psid
- 14 psi
Rationale: Both checks must close with at least 1.0 psid to ensure proper
function.
7. A failing first check valve in an RP typically causes:
- No change in zone pressure
- Decreased outlet pressure
- Relief valve discharge
- Increased inlet pressure
Rationale: If check #1 leaks, the zone pressure rises, causing relief
discharge.
- Which tool is required to measure check valve performance?
- Flowmeter
- Thermometer
- Differential pressure gauge
- Volt meter
- / 3
Rationale: Differential gauges read psid across checks and relief valves.