EPA Section 608 Type III Certification Exam Practice Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- What type of appliance is considered low-pressure under EPA Section
- Small window air conditioner
- Residential refrigerator
- Centrifugal chiller
- Split-system heat pump
- What is the typical pressure of R-123 at 80°F?
- 118 psig 1 / 4
608?
Low-pressure appliances operate below 30 psig; centrifugal chillers use R-11, R-123, etc., which are low-pressure refrigerants.
- 124 psig
- 15 psig
- 195 psig
- When evacuating a low-pressure system, the required vacuum level is
R-123 has a low vapor pressure of about 124 psig at 80°F, consistent with low-pressure systems.
measured in:
- Inches of water column
- Inches of mercury above zero
- Inches of mercury vacuum
- Microns absolute pressure
- What is the maximum allowable leak rate for low-pressure appliances?
- 10% per year
- 15% per year
- 10% per year
- 30% per year
- Which refrigerant is commonly used in low-pressure chillers?
EPA mandates evacuation requirements in inches of mercury vacuum for Type III.
The EPA leak rate threshold for low-pressure systems is 10% per year.
A. R-410A
B. R-22
C. R-123 2 / 4
D. R-404A
R-123 is widely used in centrifugal chillers as a low-pressure refrigerant.
- What is the purpose of a purge unit on a low-pressure system?
- Add oil
- Control temperature
- Remove non-condensables
- Add refrigerant
- What can cause high system pressure in a low-pressure chiller?
- Low water temperature
- Excessive air in system
- Low refrigerant charge
- Faulty TXV
- What is a key indication of non-condensables in a low-pressure chiller?
- High suction pressure
- High condenser pressure
- Low evaporator pressure
- Low oil pressure
Purge units remove air and other non-condensable gases from the chiller to maintain efficiency.
Air and other non-condensables raise condenser pressure in low- pressure systems.
Non-condensables collect in the condenser, increasing pressure. 3 / 4
- Before recovering refrigerant from a low-pressure chiller, the water
box should be:
- Left open
- Isolated and drained
- Heated
- Pressurized
- What refrigerant state is typically recovered from low-pressure
- Liquid only
- Vapor only
- Both liquid and vapor
- None
- When is refrigerant recovered as vapor from a low-pressure
- When liquid is exhausted
- When system pressure is below atmospheric
- When the chiller is running
- When oil is added
- / 4
Isolating and draining prevents water contamination or pressure damage during recovery.
systems?
Recovery occurs from both liquid and vapor phases to remove all refrigerant.
system?
Below atmospheric pressure, only vapor recovery is possible.