FDNY S99 Verification of Corrected Fire Alarm System Defects (Citywide) Practice Exam Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- A building’s fire alarm system required by code must be inspected and
- Monthly
- Quarterly
- Semi-annually
- Annually
- When verifying corrective action on a previously cited fire alarm
tested at least how often?
B Quarterly testing is the minimum frequency required for routine fire alarm system inspection and testing under citywide maintenance requirements.
system defect, the inspector must ensure that: 1 / 4
- The system panel displays “Normal” status.
- The fire alarm control panel still shows “Trouble” but has a note.
- Only manual pull stations are tested.
- Notification appliances are disabled during the test.
- Under the applicable codes, a fire alarm system’s backup power
A A “Normal” status confirms that all faults have been cleared and the system is restored to full operational condition.
supply must sustain full load operation for at least:
- 15 minutes
- 30 minutes
- 60 minutes
- 90 minutes
- Which of the following defects would prevent certification of
- A missing cover on a junction box with wiring intact and secured.
- A supervisory device still showing “Supervisory” status.
- A broken lens on a hallway strobe accessory.
- A manual pull station missing directional signage, but pull station 2 / 4
C Code mandates require backup power that can support the system under full load for a minimum of 60 minutes following a power failure.
correction?
functional.B A supervisory condition indicates the system is not in fully normal status; the defect must be cleared to certify correction.
- The audible volume level of a fire alarm horn in a residential corridor
must be:
- At least 65 dBA at 10 ft.
- At least 75 dBA at 10 ft.
- At least 85 dBA at 10 ft.
- At least 95 dBA at 10 ft.
- When a previously nonfunctional manual pull station is replaced, the
C Codes require audible devices to produce a minimum of 85 dBA at 10 feet to ensure adequate occupant warning.
inspector must verify:
- The new device is painted the same color as the wall.
- The new device activates the fire alarm control panel and causes full
- The new device has a removable break glass covering.
- The new device is mounted within 8 feet of the floor.
system alarm.
B Functionality test ensures that the replacement correctly interfaces with and initiates the fire alarm system. 3 / 4
7. A “Trouble” signal on a fire alarm control panel indicates:
- A fire has been detected.
- The system is in supervisory mode.
- There is a fault or impairment in the system.
- The system passed testing.
- For which of the following conditions can a temporary variance be
- A totally nonfunctional fire alarm system.
- Broken fire alarm control panel with no backup panel.
- A missing battery cover on backup battery cabinet.
- Entire alarm wiring exposed in a public corridor.
- After correcting a water-flow supervisory device defect, what must the
- Document only the date of correction.
- Verify that the water-flow signal is properly supervised and sends a
- Reset the system and leave it untested.
- / 4
C “Trouble” status specifically denotes a fault such as wiring, power, or device failure that affects system integrity.
granted rather than requiring immediate correction?
C Minor defects like a missing battery cover may allow temporary variance, assuming no hazard to system operation.
inspector do?
supervisory signal when tested.