- Which NFPA standard governs wet chemical extinguishing systems for
commercial cooking?
A. NFPA 10
B. NFPA 17
C. NFPA 17A
D. NFPA 96
Answer: C
Rationale: NFPA 17A specifically covers wet chemical extinguishing
systems.
- The primary extinguishing agent in most commercial cooking wet
chemical systems is: 1 / 4
- Halon 1211
- Water mist
C. CO₂
- Potassium-based solution
Answer: D
Rationale: Wet chemical systems rely on potassium salts for saponification
of hot grease.
- What process converts hot grease to a soapy layer during
- Oxidation
- Combustion
- Emulsification
- Saponification
extinguishment?
Answer: D
Rationale: Potassium-based agents react with fats to create a non-
flammable soapy foam layer.
- How often must commercial cooking exhaust systems be inspected?
- Monthly
- Every 6 months
- Annually
- Every 2 years
Answer: B
Rationale: FDNY and NFPA 96 require semiannual inspections. 2 / 4
5. Fusible links in a wet chemical system must be replaced:
- Only when damaged
- Every 5 years
- Every 6 months
- Every 3 months
Answer: C
Rationale: Fusible links are replaced at each semiannual inspection.
6. The manual pull station for the system must be located:
- Next to the fryer
- Inside the hood
- Above the cookline
- 10–20 ft from cooking appliances
Answer: D
Rationale: Manual pulls must be accessible yet away from immediate fire
danger.
7. Upon system activation, gas and electric power to appliances must:
- Stay on
- Reset automatically
- Shut off
- Switch to low power
Answer: C
Rationale: Fuel shutoff is required to stop heat production. 3 / 4
8. The test method for verifying nozzle alignment is:
- Ultrasonic testing
- Visual inspection
- Pressure test
- Thermal imaging
Answer: B
Rationale: Technicians must visually verify proper nozzle orientation.
9. System cylinders must be hydrostatically tested every:
- 2 years
- 3 years
- 12 years
- 15 years
Answer: C
Rationale: NFPA requires a 12-year hydro test for wet chemical cylinders.
10. The K-class portable extinguisher must be located within:
- 100 ft
- 50 ft
- 20 ft
- 30 ft
Answer: D
Rationale: NFPA 10 requires K-class units within 30 ft of cooking
equipment.