A facility that provides supervised and personal care on a 24 hour basis for more than 5 children 2 1/2 years of age or less shall be classified as ___? - CORRECT ANSWER: Group I-2
A fire alarm system which serves contiguous or noncontiguous properties under one
ownership is considered? - CORRECT ANSWER: Proprietary system
According to the IBC, which Use Groups which have required fire alarm systems shall utilize visible notification appliances? - CORRECT ANSWER: ALL use groups require visible notification appliances
Activation of the initiating device shall occur within ___ of water flow at the alarm-
initiating device. - CORRECT ANSWER: 90 seconds
Air sampling network piping shall be conspicuously identified at? - CORRECT
ANSWER: Changes in direction,
Each side of penetrations, Intervals not to exceed 20ft
All fire alarm system wiring shall be___. - CORRECT ANSWER: Supported by the
permanent building structure
An initiating device which is destroyed as a result of operation is what type? -
CORRECT ANSWER: Nonrestorable
- / 2
Consider a circuit of 1000 feet (total) of coated 18 AWG FPL from a 24 VDC FACP to an initiating device, with a circuit amperage of 1 amp. At 75C, what voltage is present at the
device? - CORRECT ANSWER: I x R = Voltage Drop
- A x 8.1 ohms
8.1 v 24 v - 8.1 ohms = 15.9 v
Consider a Group M Use Group where the entire building is 1 story at the level of exit discharge. At what occupant load is a fire alarm system required? - CORRECT
ANSWER: 500
Consider a Group R-1 with 80 sleeping units. How many of the rooms shall be equipped with visible alarm notification appliances activated by both the in room smoke alarm and
the building fire alarm system? - CORRECT ANSWER: 9
Consider a simple series circuit with a 24VDC power supply and a single 240 ohm
resister. What is the current for this circuit. - CORRECT ANSWER: .10 amps
(24v/240ohm = .10 amp)
Duct smoke detectors are required to ___? - CORRECT ANSWER: Be connected to the
building fire alarm system
Equipment constructed and installed in conformity with NFPA 72 shall be? - CORRECT
ANSWER: Listed
Fire power limited cabling used for runs between floors shall be of what type? -
CORRECT ANSWER: FPLR and FPLP
For fire power limited cable what is the smallest multiconductor size and smallest single
conductor size? - CORRECT ANSWER: 26 AWG multiconductor,
18 AWG single conductor