IEC 4 TH
YEAR ACTUAL EXAM WITH VERIFIED
QUESTIONS AND CORRECT ANSWERS ||
GUARANTEED PAS S | ALREADY GRADED A + |
LATEST VERSION /
What is the demand load for eighty receptacles located in a 15,000-square-foot office building?
Select one:
- 15,000
- 12,200
- 180
- 14,400 - ANSWER-a. 15,000
For a fire alarm system, an SLC ___ allowed to be T-Tapped.
Select one:
- is
- is not - ANSWER-a. is
A ___ is an example of a fire alarm system initiating device.
Select one:
- bell
- heat detector - ANSWER-b. heat detector 1 / 4
Determine the minimum size THW copper branch-circuit conductors the NEC® requires to feed a 3-phase, continuous duty motor that draws 70 amps per phase.Assume terminations are rated at 75ºC.
Select one:
- 4 AWG
- 2 AWG
- 3 AWG
- 1 AWG - ANSWER-c. 3 AWG
A feeder supplying two continuous duty, induction type, Design B, 208-volt, three- phase motors (one 10 hp and one 71/2 hp) shall have a minimum ampacity of ___ amperes.
Select one:
- 62.7
- 55
- 68.75
- 38.5 - ANSWER-a. 62.7
An attachment plug and receptacle may be permitted to serve as a motor controller if the motor is portable and has a maximum rating of ___ hp.
Select one:
- 1/3
- 1/4
- 2
- 1/2
- 1/8 - ANSWER-a. 1/3 2 / 4
Where motors are provided with terminal housings, the housings shall be ___ and of substantial construction. I. nonmetallic II. metal
Select one:
- I only
- II only
- either I or II
- neither I nor II - ANSWER-b. II only
Branch-circuit conductors that supply a single motor used in a continuous duty application shall have an ampacity of not less than ___ of the motor's full-load current rating as determined by 430.6(A)(1).
Select one:
- 190%
- 150%
- 50%
- 58%
- 125% - ANSWER-e. 125%
What is the full load current of a 30 hp, 230-volt, 3-phase, synchronous motor with a 90% power factor?
Select one:
- 76.23 amps
- 86.62 amps
- 63 amps
- 69.3 amps - ANSWER-d. 69.3 amps
- / 4
Determine the minimum size THWN copper feeder conductors required by the NEC® to supply the following 480-volt, continuous duty, 3-phase, induction-type, design B motors* 1 - 40 hp * 1 - 50 hp * 1 - 60 hp
Select one:
- 3/0 AWG
- 4/0 AWG
- 250 kcmil
- 2/0 AWG - ANSWER-b. 4/0 AWG
What size THHN copper transformer secondary conductors will be required to feed a 3-phase, 30 hp, 480-volt motor load? The secondary conductors terminate at a fusible disconnect with 70-amp fuses. The - transformer primary is supplied by a 12,470-volt circuit protected with 10-amp fuses.
Select one:
- 3
- 10
- 6
- 4
- 8 - ANSWER-d. 4
A 50 hp 230-volt, 3-phase squirrel cage motor has a full-load current of ___ amps.
Select one:
- 143
- 802
- 130
- 114
- 179 - ANSWER-c. 130
- / 4