API 653 EXAM CLOSED BOOK ACTUAL EXAM
QUESTIONS AND CORRECT ANSWERS -
ALREADY GRADED A+
When is it necessary to install a new bottom plate over an existing bottom plate, a suitable ______ material cushion such as sand, gravel or concrete shall be used between the old bottom and the new bottom.
- drainage
- compacted
- Non-conductive
- Non-corrosive - ANSWER-D
How many settlement survey points are required for an AST that is 180 feet in diameter?
N=D/10
- 12
- 19
- 18
D) 10 - ANSWER-C
What welds do not require welder's identification? 1 / 4
Page 2 of 74
2
- All welds require identification
- Vertical welded joints which are located within the final shell course since this course will be
- Roof plate welds and flanges-to-Nozzle-neck welds
- Roof Plate welds and bottom plate welds - ANSWER-C
subjected to relatively low stresses
When shall measurements be taken to verify tolerances of reconstructed tanks?
- After hydrostatic testing
- Before hydrostatic testing
- After lay out of all plates
- After fit-up and tack welding used for alignment purposes - ANSWER-B
Under what condition may magnetic particle examination be performed on a part with a coating such as paint left on the part?
- It must be demonstrated, in accordance with Mandatory Appendix II, that indications can be
- It must be demonstrated, in accordance with ASME Section VIII, Div 2, that indications can be
- It must be demonstrated, in accordance with Mandatory Appendix I, that indications can be
detected through the maximum coating thickness applied
detected through the maximum coating thickness applied
detected through the maximum coating thickness applied 2 / 4
Page 3 of 74
3
- All coatings shall be removed prior to magnetic particle examination, the coatings could
mask discontinuities - ANSWER-C
A properly selected, applied, and maintained internal bottom lining proves leak prevention by____.
- Limiting internal corrosion of the steel tank bottom
- Creating a cathodic protection barrier on the internal surface
- Enhancing the effectiveness of the external cathodic protection system
- Limiting internal corrosion of the support columns and landings pads - ANSWER-A
Each welder and welding operator shall be assigned____.
- only one joint to ensure traceability
- An identifying number, letter, or symbol
- A specific welding machine
- Weld joints on only side of the tank - ANSWER-B
Soil corrosion appears as external thinning with localized losses due to:
- Grooving
- Acid Etching 3 / 4
Page 4 of 74
4
- Erosion
- Pitting - ANSWER-D
The use of oiled sand beneath tank bottoms does not eliminate the need for cathodic
protection and in fact may cause cathodic to be less effective because:
- the oiled sand has higher resistivity
- The sand is unable to conduct electrical current
- The oil acts as an insulator and block current flow
- The oil creates a vapor bearer entrapping water and contaminants next to the tank bottom. -
ANSWER-A
Welder qualification tests conducted by one manufacturer:
- Qualifies a welder or welding operator to do work for another manufacturer
- qualifies a welder or welding operator to do work for another manufacturer provided both
- Shall not qualify a welder or welding operator to do work for another manufacturer
manufacturer are working in the dame tank farm
D)Shall not qualify a welder or welding operator to do work for another manufacturer unless the welding procedures are identical - ANSWER-C
API 653 defines a "Storage tank engineer" as:
- A registered professional engineer in structural steel fabrication
- / 4