ASSE 15000 PRACTICE TEST 3 NEWEST ACTUAL /
WITH QUESTIONS AND ANSWERS VERIFIED/GRADED A+
In evaluating whether changes to a building will require modifications to the sprinkler system, all of the following would require reevaluation except. - ----Answers--- Occupancy changes such as an insurance firm moving out and a law office moving in.
When using a pitot or flowmeter and pressure gauges to test a hose connection pressure regulating device, the findings
should be compared to the following data: - ----Answers---
Previous test resluts and hydraulic demand at the test location
Open grate flooring over ___ ft. in width shall require sprinkler protection below the grating. - ----Answers---4
The means to fill a steel tank shall be sized to fill the tank in a maximum time of ____ hours. - ----Answers---.8
At what interval shall compressed air foam generating equipment and accessories be inspected? - ----Answers--- Annually
- / 3
All master pressure-regulating devices shall be inspected weekly to verify that the devices are in the following condition
except: - ----Answers---properly supervised
When a suction tank supplies a fire pump, the control valve should be located as close as possible to the _____. - ---- Answers---tank
The maximum size pipe that may be supported by a toggle in metal lath and plaster ceilings is - ----Answers---1-1/2 inch
Given that " Circulating Closed-Loop Sprinkler Systems" are
not mentioned in NFPA 25, which of the following is true: - ---
-Answers---.Circulating Closed-Loop Sprinkler Systems are beyond the scope of NFPA 25.
The hydraulic design information sign for the automatic and semiautomatic standpipe systems shall be located at the _____.
- ----Answers---water supply control valve
According to NFPA 20 the minimum gauge pressure, at the pump suction flange, required with all pumps running at 150% capacity? - ----Answers---0
Quick response sprinklers shall be tested or replaced after: -
----Answers---20 years
- / 3
Preaction systems shall be tested once every ___ for air leakage. - ----Answers---3 years
What is the maximum protection area for standard sprinklers in light hazard, unobstructed construction? - ----Answers--- 225 sq ft
Pressure acting on a point in the system with no flow being delivered is called _____ - ----Answers---static
A variable speed fire pump is defined as a fire pump with a ___.
- ----Answers---variable speed sensing limiting control or
self -regulating variable speed fire pump unit
All residential sprinklers within a compartment must have a temperature rating within __ of one another. - ----Answers--- 20 degrees
The operation of high expansion foam systems shall be - ---- Answers---Automatic
A _____ fitting is used when the pipe size is different than the pump suction side. - ----Answers---eccentric tapered reducer or increaser
The automatic filling mechanism shall activate a maximum of _____ below the overflow level. - ----Answers---4"
- / 3