Florida Certified Electrical Contractor Exam Questions And Correct Answers (Verified Answers) Plus Rationale2026 Q&A| Instant Download Pdf
- Florida Electrical Contractor licensing is regulated by which
- Florida Department of Labor
- Florida Electrical Board
- Florida Department of Business and Professional Regulation (DBPR)
- Florida Construction Licensing Bureau
authority?
Rationale: DBPR manages licensing and enforcement for all certified
contracting professions.
2. The NEC is primarily concerned with:
- Utility provider design standards
- Safety of electrical installations
- Design aesthetics
- Energy efficiency standards only
Rationale: NEC’s core purpose is practical safeguarding of persons and
property.
- What is the minimum size grounding electrode conductor for a 200-
amp service using copper? 1 / 3
A. 4 AWG
B. 6 AWG
C. 2 AWG
D. 8 AWG
Rationale: NEC Table 250.66 specifies 6 AWG copper for 2/0 service
conductors (200A).
- Which conductor is permitted to be smaller than the ungrounded
- Service entrance conductors
- Equipment grounding conductor
- Feeder conductors
- Branch circuit conductors
conductors?
Rationale: Equipment grounding conductors may be reduced per NEC
250.122.
- The minimum burial depth for rigid metal conduit under a driveway
is:
- 6 inches
- 12 inches
- 18 inches
- 24 inches
Rationale: NEC Table 300.5 requires 18 inches for rigid metal under
driveways.
- Maximum number of disconnects allowed in one service disconnect
- 4
- 5
grouping?
C. 6 2 / 3
- 8
Rationale: The “six-disconnect rule” applies per NEC 230.71.
- The ampacity of a conductor must be corrected when ambient
temperature exceeds:
A. 30°C (86°F)
B. 40°C (104°F)
C. 25°C (77°F)
D. 35°C (95°F)
Rationale: NEC ampacity tables assume 30°C; above this, correction
factors apply.
8. A GFCI device trips when current imbalance exceeds:
- 3 mA
- 2 mA
- 5 mA
- 15 mA
Rationale: Standard personnel-protection GFCIs trip at 4–6 mA.
- Which wiring method is allowed in a plenum ceiling?
- NM cable
- Plenum-rated cable (CMP)
- UF cable
- Standard THHN in no raceway
Rationale: Only plenum-rated assemblies approved for air-handling spaces
are allowed.
- Minimum working clearance in front of 480V electrical gear?
- / 3