Florida Certified Master Electrician Exam Questions And Correct Answers (Verified Answers) Plus Rationale2026 Q&A| Instant Download Pdf
- What is the minimum size copper equipment grounding conductor
required for a 200-amp feeder?
A. 6 AWG
B. 8 AWG
C. 4 AWG
D. 2 AWG
Rationale: NEC Table 250.122 specifies a 4 AWG copper grounding
conductor for 200-amp overcurrent protection.
- Underground service-lateral conductors that are not encased in
concrete must have a minimum cover of:
- 12 inches
- 18 inches
- 24 inches
- 30 inches
Rationale: NEC Table 300.5 requires 24″ cover for direct-buried service
conductors.
- The maximum number of 90° bends allowed in a single conduit run
between pull points is:
- 2
- 3
C. 4 1 / 3
- 5
Rationale: NEC 358.26 and similar articles limit total bends to 360°.
- What is the minimum ampacity required for service conductors
supplying a 120/240-V, 1-phase, 200-amp service?
A. 150 A
B. 160 A
C. 180 A
D. 200 A
Rationale: Service conductors must not be smaller than the service rating
(NEC 230.42).
- Type NM cable is NOT permitted in which location?
- Wood-framed walls
- Above suspended ceilings in dwellings
- Commercial garages
- Residential attics
Rationale: NEC 334 prohibits NM in commercial garages due to hazardous
conditions.
- What is the maximum voltage drop recommended for a branch circuit
- 2%
- 3%
- 5%
- 8%
feeder and branch combined?
Rationale: NEC FPN recommends 3% branch, 5% total.
- The grounded (neutral) conductor in a 120/240-V system must be
- Red
- White
- Blue
- Orange
identified by which color?
Rationale: NEC 200.6 requires neutrals to be white or gray. 2 / 3
8. Minimum working clearance in front of 480-V electrical panels is:
- 2 ft
- 2.5 ft
- 3 ft
- 3.5 ft
Rationale: NEC Table 110.26(A)(1) requires 3 ft for most 480-V
equipment.
- What is the maximum continuous load allowed on a 20-A branch
circuit?
A. 12 A
B. 14 A
C. 16 A
D. 20 A
Rationale: 80% rule for continuous loads (NEC 210.20).
- Which conductor material is NOT acceptable for grounding
- Copper
- Zinc-coated steel
- Aluminum
- Stainless steel
electrodes?
Rationale: NEC 250.62 prohibits aluminum for grounding electrodes due
to corrosion.
- Minimum burial depth for rigid metal conduit under a driveway?
A. 6″
B. 12″
C. 18″
D. 24″
Rationale: NEC Table 300.5 requires 24″ under driveways.
- Maximum rating for a single receptacle on a 20-amp circuit?
- / 3