G2 Exam Prep
1 / 103
- The best tool for adjusting and setting the pressure on an appliance regu- lator:
a.Manometer b.Velometer c.Psychrometer d.
An analyzer: Manometer
- 3/8 NPS black iron pipe shall?
- Not be used for propane
- Not be used in a concealed location
- Not be used for natural gas
d. Not be used for indoors: Not be used in a concealed location (6.3.9)
- A corrugated metal gas connector connected to a range must not exceed?
- 6'
- 5'
- 3'
d. 4': 6' (6.21.3)
- A manual shut-off valve shall be installed?
- only on natural gas appliances
- in either drop of riser of a residential appliance
- downstream of the union
- at the drip pocket: In either drop of riser of a residential appliance (6.18.2)
- Black iron pipe 2 1/2 NPS at 150' long shall be pressure tested to?
- The greater of 50psig or 1.5 times the maximum operation pressure for 180 minutes
- 50 psig for 180 minutes
- 1.5 times the maximum operation pressure for 180 minutes
d. 50 psig for 60 minutes: 50 psig for 60 minutes (Table 6.3)
G2 Exam Prep
2 / 103
- Buried piping or tubing shall be?
- only copper type L coated, type G coated, type K uncoated
- only copper type K, L or type G
- schedule 50 ASTM A-53
- only copper type L or G coated: Only copper type L coated, type G coated, type K
- What is pressure drop?
- The difference in the static pressure at the meter, and the working pressure at the
- The difference between the U tube manometer is the end that is open to the
- The difference between supply pressure and appliance manifold pressure when
- The difference in the working pressure at the gas meter, and the working
- Fittings used for steel piping may be made from?
- brass or iron
- copper to malleable iron
- steel and plastic
uncoated (6.2.7)
appliance regulator
atmosphere and the pressurized side when the appliance regulator is working
the appliance calls for heat
pressure at the appliance regulator: The difference in the working pressure at the gas meter, and the working pressure at the appliance regulator
d. malleable iron and steel: Malleable iron and steel (6.2.2)
- Posts protecting piping and tubing entering a building from vehicular dam- age
- clearly marked and identified with yellow paint
- Be spaced not more than 48" apart
- Buried not less than 36" below grade
- Made from 6x6 pressure treated wood: Buried not less than 36" below grade
shall be?
(6.16.15)
- The equivalent length of a 2 1/2 NPS forged tee is?
- 9.25'
- 12.4'
- 15.3'
d. 10.3': 9.25' (Table A 16)
G2 Exam Prep
3 / 103
- What is the maximum horizontal spacing of supports for N.P.S. 1 1/4 inch gas
- 8'
- 15'
- 6'
pipe?
d. 10': 10' (3m) (Table 6.2)
- When gas piping enters a building, it must?
- Enter above grade
- Be taped, painted, and sleeved
- Have a tracer wire
d. Enter below grade: Enter above grade (6.15.8)
- When sizing a branch line, what is the minimum size of job fabricated
- 2" NPS
- 3/4" NPS
- 3" NPS
welding fittings that can be used on a NPS 6 gas supply header?
d. 1/2" NPS: 3/4" NPS (6.8.8)
- A dirt pockets shall be installed at the bottom of any piping or tubing, on the
- Unit Heater
- Furnace
- Clothes dryer
final drop serving an appliance other than a(n)
d. Boiler: Clothes dryer (6.13.1)
- Direct-vent wall furnace shall use what maximum length of corrugated metal
- 6 ft.
- 4 ft.
- 8 ft.
gas connector?
d. 2 ft.: 2 ft. (6.21.3(c))
- Every gas hose and gas fitting shall have a minimum working pressure of what.
- 275 PSIG minimum or the setting of the hydrostatic relief valves.
- 350 PSIG for piping and tubing operating at a container.
G2 Exam Prep
4 / 103
- 350 PSIG
- 250 PSIG when connected to the outlet of a pump or compressor.: 350 PSIG (6.2.9)
- What are the requirements for back filling underground piping or tubing?
- It shall not have stones larger than 38 mm
- The fill material shall contain no sharp objects.
- A trench must be dug 15 inches deep
- All of the choices: The fill material shall contain no sharp objects (6.15.6)
- Question 17
- 7 Seconds
- 28 Seconds
- 14 Seconds
What is the approximate purging time for NPS 1 that is 40 feet in length?
d. 43 Seconds: 28 seconds (Annex H Table H.1)
- What is the maximum distance a readily accessible manual shut-off valve may be
- 2 ft. and identified
- 10 ft. and identified
- 25 ft. and identified
installed from an appliance?
d. 50 ft. and identified: 50 ft. and identified (6.18.2(d))
- What is the minimum unthreaded portion of a piping outlet required when
- 2 Inches
- 6 Inches
- 3 Inches
installing a gas piping through a floor for a range?
d. 12 Inches: 2 inches (6.12.2)
- When a high pressure test is required on a gas piping system, what type of
- High Pressure gas
- Static pressure using gas
- Low pressure gas
medium would you use to perform this test.
d. Air or an inert gas: Air or an inert gas
- Nesting of bushings is permitted