Question 1: By definition an "Underground Storage Tank"
includes:
- only the tank
- the tank and all connected piping
- the tank, all connected piping and dispensers
- only tanks totally beneath the surface of the ground
CORRECT ANSWER : b. the tank and all connected piping
Question 2: Which of the following is considered an
Underground Storage Tank:
- septic tank
- 500 gallon farm tank
- 2000 gallon petroleum storage tank
- 500 gallon residential heating oil tank
- | Page
CORRECT ANSWER : c. 2000 gallon petroleum storage tank
Question 3: The UST Owner or Operator must demonstrate
financial responsibility for:
- tanks holding Heating Oil used on the premises of a residence
- Residential tanks > 1,100 gallons
- Septic tanks
- tanks < 110 gallons holding a minimum concentration of
petroleum
CORRECT ANSWER : b. Residential tanks > 1,100 gallons
Question 4: Which of the following UST Systems meet the
requirement for secondary containment:
- laminated tanks
- clad tanks
- coated tanks
- double-walled tanks
CORRECT ANSWER : d. double-walled tanks
- | Page
Question 5: The following is true of spill buckets except:
- must provide drainage for spilled product into secondary
- must be tested annually
- designed to catch product spilled during disconnection of
- for temporary storage only
containment sump
delivery hose
CORRECT ANSWER : a. must provide drainage for spilled
product into secondary containment sump
Question 6: The following are approved overfill protection
systems except:
- automatic shutoff devices
- overfill alarms
- spill buckets
- ball float valves
CORRECT ANSWER : c. spill buckets
- | Page
Question 7: If equipped with an overfill alarm, it must be
located:
- so that it can be seen and/or heard from the delivery location
- within 100 feet of the delivery location
- within 50 feet of the delivery location
- Both a and c
CORRECT ANSWER : a. so that it can be seen and/or heard
from the delivery location
Question 8: According to Title 23; The following piping
components, if installed after July 1, 1987 but prior to July 1,
2003, must have secondary containment:
- vent or tank riser piping
- vapor recovery piping not designed for liquid product
- safe suction piping
- pressurized product piping