ASSE 6010 Medical Gas Systems Installer Exam Practice Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- What is the primary standard governing the installation of medical gas
and vacuum systems?
A. NFPA 54
B. NFPA 70
C. NFPA 99
D. NFPA 13
Rationale: NFPA 99, Health Care Facilities Code, sets the
requirements for medical gas and vacuum system installation and maintenance.
- What type of piping material is required for medical gas systems?
- Black steel 1 / 4
B. PVC
- Copper tube, Type K or L, cleaned for oxygen service
- Galvanized steel
Rationale: Medical gas systems must use copper tube that is cleaned
and capped for oxygen service to prevent contamination.
- Which brazing filler metal is acceptable for joining medical gas piping?
- 35% silver
- Minimum 15% silver, cadmium-free
- Tin-lead alloy
- Phosphorus-copper alloy
Rationale: Brazing must be done with a cadmium-free filler
containing at least 15% silver to prevent toxic contamination.
- What is the minimum purge gas required during brazing?
- Nitrogen or carbon dioxide
- Oil-free, dry nitrogen
- Compressed air
- Oxygen
Rationale: Dry, oil-free nitrogen is required to prevent oxidation
inside the tubing during brazing.
5. The term “cleaned for oxygen service” means the tubing is:
- Sterilized for medical use
- Coated with oil for protection
- Free of oil, grease, and other contaminants 2 / 4
- Painted and labeled
Rationale: Tubing must be free from any hydrocarbons or
contaminants that could cause combustion with oxygen.
6. Before brazing, nitrogen should be:
- Used after brazing to cool the joint
- Flowed continuously through the pipe during brazing
- Added only to oxygen lines
- Not used unless required by the manufacturer
Rationale: Continuous nitrogen flow prevents oxidation and scale
formation inside the tube during brazing.
7. The maximum operating pressure for medical air systems is typically:
- 15 psig
- 50–55 psig
- 100 psig
- 80 psig
Rationale: Medical air systems are generally regulated to maintain a
pressure between 50 and 55 psig.
- What color is used to identify oxygen pipelines?
- Yellow
- Blue
- Green (white in Canada)
- Black
Rationale: Green is the standard color for oxygen under NFPA 99. 3 / 4
- What is the identifying color for vacuum piping?
- Green
- Yellow
- Blue
- Red
Rationale: Vacuum systems are identified with yellow per standard
color coding.
- What must be done before connecting a new medical gas branch
- Flush with water
- Connect and test under full pressure
- Isolate and purge with nitrogen, then pressure test and purge
- Connect directly and label
line to an existing system?
Rationale: Isolation and purging prevent contamination and ensure
the line is clean and leak-free.
11. The final connection to a medical gas outlet shall be performed:
- By a general plumber
- By an ASSE 6010 certified installer
- By an engineer
- By a facility manager
Rationale: Only certified installers may make final connections to
ensure compliance with ASSE 6010 and NFPA 99.
- / 4