NYC MASTER ELECTRICIAN EXAM
(ELECTRICAL)Actual Exam Newest 2026-2027 Actual Exam With Complete 100 Questions And Correct Detailed Answers (Verified Answers) |Already Graded A+
Infrared Lamps for commercial and industrial heating appliances shall have over-current protection not exceeding ____ Amps. - ANSWER- 50Amps
Panel boards equipped with snap switches rated at ____ or less shall have over-current protection not exceeding 200A. - ANSWER-30Amps
For cord and plug connected electric vehicle supply equipment is used, the interrupting devices of a listed personnel protection system shall be provided and shall be located in the power supply cable not more than ____inches from the attachment plug. - ANSWER-12" inches
Equipment associated with electrical installation can be located above or below other electrical equipment within their working space when the associated equipment does not extend more than 1 / 4
pg. 2
—— inches from the front of the electrical equipment. - ANSWER-6" inches
A fixed storage type water heater of 120 gallons or less shall be considered a continuous, load and the branch circuits conductors shall have an ampacity of ____ % of the nameplate current rating -
ANSWER-125%
Ground-fault protection of equipment shall be provided from solidly grounded which electrical services of more than 150V to ground, but not exceeding 600V phase for each service disconnecting means rated at
1,000A - ANSWER-
In patient care areas, the grounding terminals of all receptacles and all non-current-carrying conductive surfaces of fixed electric equipments operating at over 600V, Likely to become energized, subject to personal contact. - ANSWER-
Service conductors installed as unjacketed multi-conductor cable shall have a minimum clearance of 3'ft from windows that are designed to be opened, doors, porches, stairs, fire escapes, or similar locations. -
ANSWER-
A hospital is a building or portion there of used for medical, psychiatric, obstetrical, or surgical care, on a 24-hour basis, of four or more patients -
ANSWER- 2 / 4
pg. 3
The dimensions of working space for access to live parts operating at 300V, nominal to ground, where there are exposed live parts on both sides of the workspace is ____ feet. - ANSWER-4' feet
Where conductors or cables are installed in conduits exposed to direct sunlight on or above rooftops, the ambient temperature shall be increased by 60F where the conduits are less than 1/2"inch from the rooftop. - ANSWER-
What is the feeder or service calculated load for a waste disposal (940VA),dishwasher (1250VA), a trash compactor (1100VA), and a water heater (4500VA)? 5843VA - ANSWER-
Exposed live parts of motors and controller operating at ____ Volts or more between terminals shall be guarded against accidental contact by enclosure or by location. - ANSWER-50Volts
The authority having jurisdiction has the responsibility for making interpretations of rules, for deciding upon the approval of equipment and materials, for waiving specific requirements in the code permitting alternate methods and materiel if safety is maintained. - ANSWER-
Outdoor electrical vehicle charging sites, unless specifically listed for the purpose and location, the coupling means of the electric vehicle supply equipment shall be stored or located at a height of not less than 3 / 4
pg. 4
____ inches and not more than ____ft. - ANSWER-24"inches and not more than 4'feet
In NEC, the words "____, ____ ____ indicate a mandatory requirement.
- ANSWER-"Shall, Shall Not"
When the code uses the words "____ be____" it means the identified actions are allowed but not required, and they may be options or alternative methods. - ANSWER-"Shall be Permitted"
For switchboard that are not totally enclosed, in a space of ____"inches or more shall be provided between the top of the switchboard and any combustible ceiling. - ANSWER-36"inches (3ft)
Overhead feeder conductors shall have a minimum ____feet vertical clearance over residential property and driveways, as well as those commercial areas not subject to truck traffic, where the voltage is limited to 300V to-ground. - ANSWER-12'feet
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with conductors of Class 1 or electric light or power conductors, unless ____ ____ ____. - ANSWER- Separated by barrier
- / 4