Wastewater Facilities Operator Class II Practice Exam Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- What is the primary purpose of a grit chamber in a wastewater facility?
- Remove dissolved solids
- Reduce BOD
- Remove heavy inorganic materials
- Remove pathogens
Answer: C
Rationale: Grit chambers remove heavy inorganic materials like sand and
gravel to protect downstream equipment.
- What is the typical detention time in a primary clarifier? 1 / 4
- 5–10 hours
- 30–60 seconds
- 1.5–2.5 hours
- 8–12 hours
Answer: C
Rationale: Primary clarifiers generally operate with a 1.5–2.5 hour
detention time for proper settling.
- Which process is used to biologically remove BOD?
- Screening
- Grit removal
- Activated sludge
- Disinfection
Answer: C
Rationale: Activated sludge introduces microorganisms that consume
organic matter, reducing BOD.
4. In activated sludge, the term F/M ratio refers to:
- Flow/Mixing
- Food/Microorganism
- Filtration/Movement
- Fat/Microbe 2 / 4
Answer: B
Rationale: F/M is the ratio of organic load (food) to biomass
(microorganisms), controlling process stability.
5. A low DO level in an aeration tank typically causes:
- Reduced sludge age
- Increased nitrification
- Filamentous bulking
- Lower MLSS
Answer: C
Rationale: Filamentous organisms thrive under low DO, causing bulking.
6. Chlorine is most effective as a disinfectant when pH is:
- Above 9
- Neutral
- Below 7
- Between 10–12
Answer: C
Rationale: Lower pH favors hypochlorous acid formation, the most
effective disinfectant form.
- What is the purpose of a trickling filter distributor arm? 3 / 4
- Remove solids
- Evenly spread wastewater over media
- Remove pathogens
- Store sludge
Answer: B
Rationale: Distributor arms ensure uniform distribution for effective
biological treatment.
8. The sludge blanket in a secondary clarifier should be:
- Touching the underflow
- In the scum trough
- Low and stable
- Floating
Answer: C
Rationale: A stable, low sludge blanket prevents solids overflow and
ensures proper separation.
- What is the typical DO concentration in an activated sludge aeration
- 0.5 mg/L
- 2 mg/L
- 6 mg/L
- / 4
tank?