ASSE 5130 Backflow Prevention Assembly Repairer Exam Practice Questions And Correct Answers (Verified Answers) Plus Rationales 2026 Q&A | Instant Download Pdf
- What is the main purpose of a backflow prevention assembly?
- To increase water pressure
- To prevent reverse flow of water into the potable supply
- To filter out impurities
- To regulate temperature
Answer: B
Rationale: Backflow prevention assemblies are designed to stop
contaminated or non-potable water from reversing into the clean water system.
- Which condition causes backpressure backflow?
- Negative pressure in the supply 1 / 4
- A decrease in downstream pressure
- Pressure downstream exceeds supply pressure
- A vented condition in the supply line
Answer: C
Rationale: When downstream pressure becomes higher than supply
pressure, water can flow backward, causing backpressure backflow.
- The check valves in a Reduced Pressure Principle Assembly must close
tight when tested at:
- 0.5 psi
- 1.0 psi
- Differential pressure greater than 1.0 psi
- No differential pressure
Answer: C
Rationale: The check valves must maintain a differential pressure greater
than 1.0 psi to ensure proper sealing.
- Which component of a Double Check Valve Assembly (DCVA) prevents
- Two independently acting check valves
- Air inlet valve
- Relief valve
- Shutoff valves only 2 / 4
backflow?
Answer: A
Rationale: The two check valves act independently to prevent reverse flow,
ensuring redundancy.
5. The relief valve in an RP assembly opens when:
- There is a pressure drop across the first check
- The first check leaks and the pressure between checks exceeds supply
- The supply pressure increases suddenly
- Downstream pressure is higher than supply
Answer: B
Rationale: The relief valve opens when the pressure in the zone exceeds
the supply pressure due to leakage past the first check.
- What is the minimum differential pressure required across each check
- 0.5 psi
- 1.0 psi
- 2.0 psi
- 3.0 psi
valve in a DCVA during testing?
Answer: B
Rationale: Each check must close tight with a minimum of 1.0 psi
differential pressure to pass. 3 / 4
- A repairer finds debris under the check valve disc. What is the most
- Replace the entire assembly
- Clean the check seat and disc
- Replace the disc with an oversized one
- Install a new test cock
appropriate repair step?
Answer: B
Rationale: Debris on the seat prevents sealing; cleaning the seat and disc
usually resolves the issue.
- What type of backflow results when the supply pressure drops below
- Backpressure
- Backsiphonage
- Cross-connection
- Pressure surge
atmospheric pressure?
Answer: B
Rationale: Backsiphonage occurs when negative pressure draws water
backward into the potable system.
- / 4